Thanks to the smart monitoring platform, Deye full series inverter products support remotely shutdown immediately when accident occurs.Setting parameters and FW update remotely, which makes PV plant O&M easier.
● Colorful touch LCD, IP65 protection degree
● 6 time periods for battery charging/discharging
● Max. charging/discharging current of 290A
● Support storing energy from diesel generator
● AC couple to retrofifit existing solar system
● Max. 16 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel
Model | SUN-12K-SG01LP1-EU | SUN-14K-SG01LP1-EU | SUN-16K-SG01LP1-EU | |||||||
Battery Data | ||||||||||
Battery Type | Lead-acid or Lithium-ion | |||||||||
Battery Voltage Range (V) | 40-60 | |||||||||
Max. Charging Current (A) | 220 | 250 | 290 | |||||||
Max. Discharging Current (A) | 220 | 250 | 290 | |||||||
External Temperature Sensor | Yes | |||||||||
Charging Curve | 3 Stages / Equalization | |||||||||
Charging Strategy for Li-Ion Battery | Self-adaption to BMS | |||||||||
PV String Input Data | ||||||||||
Max. DC Input Power (W) | 15600 | 18200 | 20800 | |||||||
Max. DC Input Voltage (V) 500 | ||||||||||
Start-up Voltage (V) | 125 | |||||||||
MPPT Range (V) | 150-425 | |||||||||
Rated DC Input Voltage (V) | 370 | |||||||||
PV Input Current (A) | 26+26+26 | |||||||||
Max. PV ISC(A) | 44+44+44 | |||||||||
No.of MPP Trackers | 3 | |||||||||
No.of Strings per MPP Tracker | 2+2+2 | |||||||||
AC Output Data | ||||||||||
Rated AC Output Active Power (W) | 12000 | 14000 | 16000 | |||||||
Max AC Output Active Power (W) | 13200 | 15400 | 17600 | |||||||
Rated AC Output Current (A) | 54.5/52.2 | 63.6/60.9 | 72.7/69.6 | |||||||
Max AC Output Current (A) | 60/57.4 | 70/67 | 80/76.5 | |||||||
Max. Continuous AC Passthrough (A) 100 | ||||||||||
Peak Power (Off Grid) | 2 time of rated power, 5 S | |||||||||
Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | |||||||||
Power Factor | 1 | |||||||||
Output Frequency and Voltage | 50/60Hz; L/N/PE 220/230Vac | |||||||||
Grid Type | Single Phase | |||||||||
Total Harmonic Distortion (THD) | <3% (of nominal power) | |||||||||
DC Current Injection | <0.5% In | |||||||||
Backup Data | ||||||||||
Backup Power (W) | 10000 | 12000 | 14000 | |||||||
Backup Rated Current (A) | 45.5/43.5 | 54.5/52.2 | 63.6/60.9 | |||||||
Backup UPS | 4ms Automatic switchover time | |||||||||
Efficiency | ||||||||||
Max. Efficiency | 97.60% | |||||||||
Euro Efficiency | 96.50% | |||||||||
MPPT Efficiency | 99.90% | |||||||||
Protection | ||||||||||
Integrated | Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, |
|||||||||
Output Shorted Protection, Surge Protection | ||||||||||
Over Voltage Category | DC Type II/AC Type III | |||||||||
Certifications and Standards | ||||||||||
Grid Regulation | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549- 1, G98, G99, C10- 11, UNE217002, NBR16149/NBR16150 |
|||||||||
Safety EMC / Standard | IEC/EN 61000-6- 1/2/3/4, IEC/EN 62109- 1, IEC/EN 62109-2 | |||||||||
General Data | ||||||||||
Operating Temperature Range (C) | -40-60℃, >45℃ Derating | |||||||||
Cooling | Smart Cooling | |||||||||
Noise (dB) | ≤30 dB | |||||||||
Communication with BMS | RS485; CAN | |||||||||
Weight (kg) | 48.5 | |||||||||
Cabinet Size (WxHxD mm) | 464×763×282 (Excluding Connectors and Brackets) | |||||||||
Protection Degree | IP65 | |||||||||
Installation Style | Wall-mounted | |||||||||
Warranty | 5 Years (10 Years Optional) |